APC MGE Galaxy 3500 (3 Phase) 20kVA UPS from APC by Schneider Electric offers a new way for electrical contractors and facility managers to achieve reliable and cost-effective protection for mission-critical applications. A modular design with factory installed, swappable batteries and electronics reduces installation time - making the Galaxy 3500 easy to deploy and maintain. The product features an excellent 96 percent (TUV certified) efficiency, resulting in reduced total cost of ownership and annual customer savings. The Galaxy 3500 ships with dual mains input and a built-in maintenance bypass switch, increasing system availability. The Environmental Monitoring Card is supplied with the product, as well as a start-up service to ensure the right configuration from the start. And for demanding industrial environments, reliability features include IP51 protection, standard 2-millimeter thick steel plate enclosure, and user replaceable air filters.
Technology: | Galaxy 3500 |
Rating: | 10/15/20/30/40 kVA |
Configuration: | Tower |
*This is a special order item. Please email us at info@criticalpowersolutions.com.au for pricing and availability*
Technical Specifications
Output
Nominal Output Voltage (V) |
3:1 (220/230/240V) 3:3 (380/400/415V) Three Phase + Neutral |
Efficiency at Full Load (AC-AC at Nominal Mains) | 95.8% |
Efficiency at 50% Load (AC-AC at Nominal Mains) | 95.5% |
DC - AC Nominal Battery Voltage | 95.2% |
Load Power Factor | 0.5 leading to 0.5 lagging |
Output Frequency | Mains sychronized in normal operation 50 Hz +/- 0.05% free-running |
Output Voltage Tolerance | +/- 1% static, +/- 5% at 100% load step |
Input
Input Voltage (V) | 380/400/415 V (three phase + neutral) |
Frequency (Hz) | Sychronized to mains |
Input Power Factor | > 0.98 at load < 50% |
Input Voltage Tolerance Utility Operation | 304V to 477V at full load, 200V to 477V at half load (for 400V) |
Dual Mains Input | Yes |
Input Voltage Tolerance Bypass | +/- 10% standard +/- 4, 6, 8, 10% (programmable) |
Backfeed Protection | Built-in backfeed contractor |
Communications & Management
Communication Interface | Network Management Card with environmental monitor |
Control Panel | Power view multi-function LCD, status and control console |
Emergency Power Off | Yes |
Protection
Surge Energy Rating | IEC 61000-4-5 |
Thermal, Short Circuit | Yes |
Physical
Height | 149.0 cm |
Width | 52.3 cm |
Depth | 83.8 cm |